Energy Storage Parameters |
|
Cell type |
Lithium iron phosphate |
Energy storage capacity |
40.32KWh |
Release rate |
≤1C |
Cycle times |
≥3000 times (80%) |
Input Parameter |
|
Input voltage |
380Vac±15% |
Input frequency |
50Hz |
Power factor |
≥0.99 |
Efficiency (full load) |
≥0.95 |
THD |
≤5% |
Output Parameters |
|
Output power |
30KW |
Output voltage |
DC 60-750V |
Output current |
80A |
Voltage stabilization accuracy |
<±0.5% |
Steady current accuracy |
≤±1% (output load 20%~100% rated range) |
Structural Appearance |
|
Product size |
730X580X2670m |
Protection level |
IPS4 |
Installation method |
Floor standing installation |
Gun line length |
7 meters |
Product weight |
430Kg |
Interaction Type |
|
Communication method |
4G |
Human computer interface |
21.5-inch LCD, battery display column |
Security function |
|
Safety standard |
GB/T 18487.1-2015 NB/T 33008.2-2018 |
Protection functions |
Input/output overvoltage protection, short circuit protection, over temperature protection, over-current protection, battery reverse connection protection, etc |
Output Parameters |
|
Working temperature |
-20℃-50℃ |
Working humidity |
5%-95% without condensation |
Working altitude |
≤2000m |
Cooling method |
Air cooling |
Noise coefficient |
≤65dB |
Shipping & Returns
Row content
Compatibility
Row content
1 Site selection and construction phase
Reduce power distribution requirements, quickly
deploy, improve construction efficiency.
2 operational phases
Peak shaving and valley filling to increase
electricity revenue by 50%.
3 Extended Services
Scheduling peak shaving, virtual power plants,
emergency backup power.